PROTECTA FR Acrylic

PROTECTA®FR Acrylic is employed to prevent the spreading of noise, fire and smoke through joints and openings is sound and fire classified walls and floors as well as around technical transitions.

PROTECTA®FR Acrylic hardens when it is subjected to atmospheric climates and reates a robust and durable fire seal which is also elastic.

PPROTECTA®FR Acrylic is employed with suitable filling material as rockwool etc in order to secure correct width to depth ratio and to reduce the shrinking of the joint during hardening.

Minimum depth an maximum width of the joints are included in the fitting instructions. When the joint is subjected to fire it will expand at about 180° C and efficiently prevent the flames from burning through for up to 4 hours.

Certificate Technical specification  CAD Catalogue Gallery Articles

Single sided

FIRE RESISTANCE

 Type System EI
 Linear joint < 30 mm15 mm mastics + 25 mm rockwool 120 
 Cable D < 25 mm15 mm mastics + 25 mm rockwool 60
 Steel pipe D < 219 mm15 mm mastics + 25 mm rockwool  90
 Copper pipe D < 58 mm15 mm mastics + 25 mm rockwool 120
 Ducts 1000 x 1000 mm, D < 1000 mm15 mm mastics + 25 mm rockwool 60

Double sided

 Type System EI
 Linear joint < 30 mm                                 25 mm mastics + 50 mm rockwool  240
 Linear joint < 30 mm8 mm mastics + 20 mm rockwool 90
 Cable D < 25 mm15 mm mastics + 30 mm rockwool 240
 Cable D < 55 mm9 mm mastics + 20 mm rockwool 60
 Steel pipe D < 58 mm9 mm mastics + 20 mm rockwool 90
 Steel pipe D < 219 mm15 mm mastics + 20 mm rockwool 180
 Copper pipe D < 58 mm9 mm mastics + 20 mm rockwool 120
 Plastic pipe D < 42 mm25 mm mastics + 40 mm rockwool 240

Must be used rockwool with a densiti > 128 kg/m³.
Steel an copper pipes shal be extra insulated with 40 mm thickness rockwool, 80 kg/m³, 600 mm from the wall/floor in both sides.